Advisories › Red Lion Controls › ICSA-26-281-01

Red Lion Controls N-Tron 700 Series - Update A: 7 CVEs, High 8.3

High 8.3 Oil & gas relevant ICSA-26-281-01 · Published Oct 8, 2026 · Updated Oct 15, 2026

Summary

CISA reports 7 vulnerabilities in Red Lion Controls 700 Series. Weakness types: Use of Hard-coded Credentials, Insufficiently Protected Credentials, Storing Passwords in a Recoverable Format (+4 more). Successful exploitation of these vulnerabilities could allow a malicious user to access the device and gain administrative access. This access would allow the user to view, edit, and upload configuration files. Highest CVSS v3 score: 8.3 (High), exploitable over the network.

What to do: Prioritize: Red Lion controls recommends users upgrade the N-Tron 700 Series to version 3.11.1 or greater.Red Lion controls recommends users configure or disable the SNMP communities.Red Lion controls recommends users disable access to the web GUI.
Why this matters for oil & gas: Red Lion HMIs/RTUs and cellular routers are common at remote sites.

At a glance

Vendor
Red Lion Controls
Products
700 Series
CVEs
CVE-2026-32645, CVE-2026-39460, CVE-2026-28745, CVE-2026-33367, CVE-2026-29797, CVE-2026-39453, CVE-2026-33272
Highest CVSS v3
8.3 CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:L/I:H/A:H
Highest CVSS v4
–
Known exploited (KEV)
No CVE from this advisory is on the KEV list as of the last refresh
Sectors (per CISA)
Commercial Facilities, Communications, Critical Manufacturing, Information Technology
Deployed
Worldwide
Vendor HQ
Sweden

Vulnerabilities

CVEWeaknessCVSS v3CVSS v4KEVDescription (from advisory)
CVE-2026-32645Use of Hard-coded Credentials6.0–NoDefault factory credentials with administrative access are enabled and persist even after configuring other administrator accounts.
CVE-2026-39460Insufficiently Protected Credentials8.1–NoUsernames and passwords, including the default factory credentials, are stored in plaintext within the configuration file. With administrator rights, the configuration file can be viewed through the CLI or they can be exported from the device through a TFTP transfer from the web interface. A TFTP transfer can be initiated through SNMP which does not require authentication.
CVE-2026-28745Storing Passwords in a Recoverable Format7.5–NoUsernames and passwords, including the default credentials, are stored in the configuration file using weak encryption. If the default credentials are known by a malicious user, they could obtain other credentials on the system.
CVE-2026-33367Missing Authentication for Critical Function8.1–NoSNMP can be used to perform administrative actions such as retrieving configuration files, modifying user accounts or device settings, and initiating firmware or bootloader upgrades or downgrades-all without any authentication.
CVE-2026-29797Download of Code Without Integrity Check7.1–NoNo authentication is required when updating firmware or bootloader, making it easy for malicious files to be pushed to the device. Additionally, anyone with the same software can scan a network for N-Tron devices and push/pull firmware without authenticating by using SNMP/TFTP.
CVE-2026-39453Reachable Assertion8.3–NoNavigating to a certain URL on the switch's web server causes the switch to reboot. This can be automated using a tool like curl to create DoS conditions where the switch constantly reboots.
CVE-2026-33272Authentication Bypass Using an Alternate Path or Channel4.9–NoA malicious user with physical access to the device can boot the switch from factory settings without authentication, use the default administrative credentials to obtain administrative access, and save changes to the configuration file so that they persist next time the switch boots normally.

Affected products (2)

Vendor fixes and mitigations (from advisory)

Also apply CISA's standard ICS practices: minimize network exposure, keep control networks behind firewalls and isolated from business networks, and use up-to-date secure remote access.

Sources

This page is generated automatically from the CISA advisory text. It is not a substitute for the vendor's guidance; verify affected versions and fixes at the source before making changes to control systems.

Weekly OT patch digest

Every week: the new ICS advisories that touch oil & gas gear, what they mean, and what to do. Free.

TODO: signup form not connected to a provider yet