Advisories › ABB › ICSA-26-274-03

ABB Protection and Control IED Manager PCM600: 2 CVEs, Medium 6.4

Medium 6.4 Oil & gas relevant ICSA-26-274-03 · Published Oct 1, 2026

Summary

CISA reports 2 vulnerabilities in ABB Protection and Control IED Manager PCM600. Weakness types: Incorrect Permission Assignment for Critical Resource, Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal'). Successful exploitation of these vulnerabilities could allow an attacker to escalate privileges or overwrite files. Highest CVSS v3 score: 6.4 (Medium), not remotely exploitable per its CVSS vector.

What to do: Plan: Locate the ABBPCMSchedulerService corresponding to the installed PCM600 version.
Why this matters for oil & gas: ABB (800xA, Totalflow flow computers, Ability) is common in oil & gas measurement and process control.

At a glance

Vendor
ABB
Products
Protection and Control IED Manager PCM600
CVEs
CVE-2026-15952, CVE-2026-15953
Highest CVSS v3
6.4 CVSS:3.1/AV:L/AC:H/PR:H/UI:N/S:U/C:H/I:H/A:H
Highest CVSS v4
–
Known exploited (KEV)
No CVE from this advisory is on the KEV list as of the last refresh
Sectors (per CISA)
Energy
Deployed
Worldwide
Vendor HQ
Switzerland

Vulnerabilities

CVEWeaknessCVSS v3CVSS v4KEVDescription (from advisory)
CVE-2026-15952Incorrect Permission Assignment for Critical Resource6.4–NoA vulnerability exists in the Scheduler Service installed with PCM600. The service executes under the LocalSystem account while permissions are granted to standard PCM600 users through membership in the local users group. An attacker with local access and valid user credentials may exploit this vulnerability to elevate privileges and obtain control of the affected host.
CVE-2026-15953Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')5.0–NoA vulnerability exists in the processing of PCM600 project archives files. Insufficient validation of archive entry paths may permit path traversal during extraction, potentially allowing files to be written to loca tions outside the intended extraction directory.

Affected products (1)

Vendor fixes and mitigations (from advisory)

Also apply CISA's standard ICS practices: minimize network exposure, keep control networks behind firewalls and isolated from business networks, and use up-to-date secure remote access.