Advisories › ANDRITZ › ICSA-26-225-05

ANDRITZ HIPASE-250 and 250 SCALA: 4 CVEs, High 8.1

High 8.1 ICSA-26-225-05 · Published Aug 13, 2026

Summary

CISA reports 4 vulnerabilities in ANDRITZ HIPASE-250, 250 SCALA. Weakness types: Storing Passwords in a Recoverable Format, Missing Authentication for Critical Function, Use of Hard-coded Credentials. Successful exploitation of these vulnerabilities could allow an attacker to read data from the device or gain access to affected workstations. Highest CVSS v3 score: 8.1 (High), exploitable from an adjacent network.

What to do: Prioritize: ANDRITZ has addressed these issues in version V8.00.00 (released 2024-12) and in version V8.15.00 (released 2026-07) and encourages users to keep their systems updated to the latest version (currently HIPASE-250 Version V8.15.00).

At a glance

Vendor
ANDRITZ
Products
HIPASE-250, 250 SCALA
CVEs
CVE-2026-65309, CVE-2026-65310, CVE-2026-65311, CVE-2026-65313
Highest CVSS v3
8.1 CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
Highest CVSS v4
–
Known exploited (KEV)
No CVE from this advisory is on the KEV list as of the last refresh
Sectors (per CISA)
Energy
Deployed
Worldwide
Vendor HQ
Austria

Vulnerabilities

CVEWeaknessCVSS v3CVSS v4KEVDescription (from advisory)
CVE-2026-65309Storing Passwords in a Recoverable Format7.5–NoANDRITZ HIPASE-250 (formerly 250 SCALA) in affected versions stores and transmits user passwords using a reversible format instead of a one-way password hash. This allows an attacker able to read the credential store or capture network traffic to recover all stored passwords.
CVE-2026-65310Missing Authentication for Critical Function7.5–NoANDRITZ HIPASE-250 (formerly 250 SCALA), in the default configuration of affected versions, exposes its data and configuration endpoint without any authentication and permissive CORS on every response. An unauthenticated attacker with network access can read live process values and server configuration.
CVE-2026-65311Missing Authentication for Critical Function5.3–NoThe HTTP server component of ANDRITZ HIPASE-250 (formerly 250 SCALA) in affected versions exposes an undocumented endpoint that changes the server's logging level and target without requiring authentication. A remote, unauthenticated attacker with network access to the service may suppress audit logging, potentially concealing other activity on the system.
CVE-2026-65313Use of Hard-coded Credentials8.1–NoA provisioning script used when installing HIPASE-250 (formerly 250 SCALA) engineering workstations sets a fixed, hard-coded x11vnc password. Because the same credential is applied to every workstation provisioned this way, an attacker with adjacent-network access who knows the password can gain VNC access to affected workstations.

Affected products (2)

Vendor fixes and mitigations (from advisory)

Also apply CISA's standard ICS practices: minimize network exposure, keep control networks behind firewalls and isolated from business networks, and use up-to-date secure remote access.